Permit: T11EL02787

Parcel: 136333170


Addresses:

8910 E ARBOR ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/28/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/25/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COVER PLATES NEEDED ON ALL OUTLETS
2) SECURE JUNCTION BOX FOR POOL EQUIPMENT
3) PHYSICAL PROTECT CONDUCTORS FOR OUTLETS AND SWITCHES AT BACK PATIO
4) GFI PROTECT OUTLETS AT BACK PATIO WITH WEATHERPROOF COVERS
5) MULTIPLE CONDUCTORS UNDER SINGLE BREAKER
6) SECURE PANEL AT HOUSE
7) PHYSICAL PROTECT WIRES GOING TO PANEL
8) WEATHERPROOF COVER NEEDED ON OUTLET BY A/C COMPRESSOR
9) SMOKE DETECTORS NEEDED IN ALL BEDROOMS