Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/25/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/24/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BLANK OFF OPEN SPACES AT ELECTRICAL PANEL 2) NEUTRAL (WHITE) WIRE GOING TO BREAKER HOT LEAD 3) MAXIMUM 2 NEUTRALS UNDER 1 SCREW AT NEUTRAL BAR 4) SMOKE DETECTOR IN HALLWAY TO BE OPERABLE 5) SMOKE DETECTORS NEEDED IN BEDROOMS 6) LABEL BREAKERS |