Permit: T11EL02778

Parcel: 132163160

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/14/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/29/2012 ELECTRIC - FINAL Denied WATER HTR NOT WIRED TO CODE AS PER LAST INSPECTION
10/27/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) LEFT MESSAGE 10 AM
2) 50 AMP WATER HEATER CIRCUIT, REPLACE BREAKER 30 AMP. WHITE HOT LEAD RED OR BLACK (TAPE OK)
3) PROTECT WATER HEATER LINE AND HARD WIRE
10/25/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BLANK COVER OPENINGS DEADFRONT
2) MANY OPEN CONDUCTORS IN PANEL
3) MIXED BREAKER TYPES IN PANEL AND INSTALL GENERAL PACIFIC
4) PROTECT ROMEX EXPOSED IN STORAGE ROOM FROM PHYSICAL DAMAGE
5) SECURE ALL BOXES TO CODE
6) MISSING FURNACE AND WATER HEATER. PROVIDE PERMITS FOR REPLACEMENT
7) ALL ADDITIONS SHOULD BE ON RECORD WITH PERMIT
8) NOTES 1-5 FOR POWER