Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/07/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST ADDRESS ON HOUSE 2) RE-ATTACH WATER BOND IN FRONT WATER PIPE 3) INSTALL SMOKE DETECTORS IN BEDROOMS MINIMUM 3' AWAY FROM COOLER VENTS 4) WATER HEATER NOT WIRED 5) PANEL FOR SERVICE HAS BEEN ALTERED, CANNOT MIX MANUFACTURERS/PARTS, MUST BE COMPLETE LISTED EQUIPMENT, KO'S NOT BUSHED BEHIND PANEL, GROUND ELECTRODE CONDUCTOR SPLICE MUST BE IRREVERSIBLE. GAS WIRE NEEDS TO BE STRAPPED TO WALL 6) LIGHT FIXTURE IN CLOSET NEEDS TO BE ENCLOSED TYPE 7) ROOM ADDITION BUILT IN BACK SHOULD BE ON RECORD |
|
| 10/21/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) LEFT MESSAGE 8:25 AM 2) PROVIDE ACCESS 9:30 AM |