Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BLANK COVER UNUSED OPENING IN DEAD FRONT 2) SERVICE LACKS 36" CLEARANCE PER CODE 3) ALL ADDITIONS SHOULD BE ON RECORD 4) RECALL 02090 |
|
| 10/20/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RELOCATE SMOKE ALARMS PER SPECS 2) OMIT ZIP CORD MASTER CLOSET LIGHT FIXTURE 3) REMOVE LOCK FROM SERVICE FOR INSPECTION 4) OMIT 220 TO LAUNDRY, NOT TO CODE 5) PROTECT ROMEX IN STORAGE FROM PHYSICAL DAMAGE UNDR 7' IN HEIGHT |