Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/28/2011 | ELECTRIC - FINAL | Partial Approval | ||
| 10/27/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE RISER PER CODE CLAMP SOLIDLY TO BLDG WITH 2 CLAMPS FROM BOX TO OVERHANG 2) SECURE #4 TO BLDG 3) METAL ADDESS TAG 4) PROVIDE ACORN CALMPS FOR DIRECT BURIAL AT GROUND ROD CONNECTIONS |
|
| 10/24/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED 2ND ROD AT EAST 6' AWAY FROM 1ST ROD 2) NEED GAS AND WATER BONDS |
|
| 10/19/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 3 ADDED CIRCUITS TO EXISTING PANEL NOT TO CODE. LACKS CONNECTORS 2) SECURE PANEL TO BLDG 3) GROUND WIRE VANDALIZED. INSTALL CONTINOUS GROUND WIRE TO GROUND ROD SYSTEM OR VERIFY GROUND 4) PROTECT EXPOSED ROMEX KITCHEN LIGHT SWITCH UNDER 7' FROM PHSYCIAL DAMAGE 5) SMOKE ALARM BEDROOM 6) SERVICE SHOULD BE UPRAGED OR NEW PANEL LIKE FOR LIKE. IMPROPERLY MAINTAINED SERVICE. DISCONNECT MEANS HEIGHT OVER 6"-8" |