Permit: T11EL02733

Parcel: 117080770


Addresses:

118 E 18TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/03/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/28/2011 ELECTRIC - FINAL Partial Approval
10/27/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SECURE RISER PER CODE CLAMP SOLIDLY TO BLDG WITH 2 CLAMPS FROM BOX TO OVERHANG
2) SECURE #4 TO BLDG
3) METAL ADDESS TAG
4) PROVIDE ACORN CALMPS FOR DIRECT BURIAL AT GROUND ROD CONNECTIONS
10/24/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED 2ND ROD AT EAST 6' AWAY FROM 1ST ROD
2) NEED GAS AND WATER BONDS
10/19/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 3 ADDED CIRCUITS TO EXISTING PANEL NOT TO CODE. LACKS CONNECTORS
2) SECURE PANEL TO BLDG
3) GROUND WIRE VANDALIZED. INSTALL CONTINOUS GROUND WIRE TO GROUND ROD SYSTEM OR VERIFY GROUND
4) PROTECT EXPOSED ROMEX KITCHEN LIGHT SWITCH UNDER 7' FROM PHSYCIAL DAMAGE
5) SMOKE ALARM BEDROOM
6) SERVICE SHOULD BE UPRAGED OR NEW PANEL LIKE FOR LIKE. IMPROPERLY MAINTAINED SERVICE. DISCONNECT MEANS HEIGHT OVER 6"-8"