Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T11EL02729
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/03/2011 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
11/01/2011 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
10/25/2011 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 220 AT RANGE IN APPROVED BOX 2) NOTES 1 & 2 FROM PREVIOUS 3) RELOCATE ANY SMOKE ALARM WITHIN 36" FORCED AIR REGISTER 4) REAR ADDITION MUST BE ON RECORD 5) OMIT EXPOSED WIRING AT LIVING ROOM WINDOW |
|
10/19/2011 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BLANK COVER UNUSED OPENINGS DEADFRONT 2) OMIT HAZARDOUS WIRING REAR LIGHT FIXTURE 3) HAZARDOUS WIRING EXPOSED ROMEX TO DINING ROOM OUTLET. PROTECT FROM PHYSICAL DAMAGE 4) OMIT ZIP CORD BEDROOMS CEILING FAN 5) SMOKE ALARM BEDROOM 6) REAR ADDITION WATER HEATER ROOM LACKS COMBUSTION RELIEF 7) NOTES 1-5 FOR POWER |