Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/17/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE TAPPED CIRCUIT FROM MAIN LUGS AND ADD FUSE 2) CHANGE 3 PRONG OUTLETS BACK TO 2 PRONG OR GFI'S 3) CHANGE ALL FUSES TO CORRECT SIZES IN SUB PANEL 4) MOVE SMOKIES UP TO 6" BELOW CEILING |