Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/26/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/24/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO PLANS ON SITE 2) GROUNDING ELECTRODE SYSTEM NEEDED AT SUB PANEL 3) PACK SEAL OFF BEFORE POURING 4) UN-COVER UNDERGROUND LAST INSPECTION 5) NEED ACCESS TO PUMP/BLOWER ? EQUIPMENT TO INSPECT 6) LABEL SUB PANEL COVER |
|