Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T11EL02655
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/25/2011 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
10/13/2011 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) CALL RAY MAJUTA WITH INFORMATION FROM PREVIOUS INSPECTIONS |
|
10/12/2011 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT RUN LOAD CONDUCTORS THRU METER SECTION 230 NEC 2) CIRCUIT BREAKERS TO BE ON SAME MANUF. AS PANEL 110.3 NEC 3) EXPOSE GROUND RODS/WATER AND GAS PIPE BONDING 4) PROVIDE 6' LADDER FOR GUTTER INSEPCTION AND OPEN GUTTER 5) PROVIDE LISTING INFO AND MANUF. DATA MISSING FROM COVER 6) 8' CLEARANCE OVER ROOF OF 2ND UNIT PER 225 NEC 7) VERIFY UNIT #1 UPGRADE PERMIT AND INSPECTION 8) SCREW FOR DEAD FRONT COVER MISSING 9) BONDING IN GUTTER PER 250.92 NEC (VERIFY) 10) PROVIDE NAME AND PHONE NUMBER OF LICENSED CONTRACTOR THAT DID THE WORK 11) ALSO EXPOSED CONDUCTORS COMING OUT OF 6 X 6 J-BOX ABOVE SERVICE EQUIPMENT |