Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2011 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 10/07/2011 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RISER BRACE TO BE LISTED 2) NEW FEEDERS TO LOW ACROSS ROOF UNIT IN FRONT, 8' ALSO NEED EQUIP. GROUND PER 230 AND 250 NEC 225.19 3) 2-100 AMP MAINS IN A 100 AMP PANEL, (MAIN SES). PROVIDE LOAD CALCS, TO INSURE NO OVER LOAD AND SUBMIT FOR APPROVAL 4) INSTALL GROUNDING ELECTRODE SYSTEM 2ND UNIT PER 250.32 NEC |