Permit: T11EL02635

Parcel: 119041620

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/12/2011 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
10/07/2011 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RISER BRACE TO BE LISTED
2) NEW FEEDERS TO LOW ACROSS ROOF UNIT IN FRONT, 8' ALSO NEED EQUIP. GROUND PER 230 AND 250 NEC 225.19
3) 2-100 AMP MAINS IN A 100 AMP PANEL, (MAIN SES). PROVIDE LOAD CALCS, TO INSURE NO OVER LOAD AND SUBMIT FOR APPROVAL
4) INSTALL GROUNDING ELECTRODE SYSTEM 2ND UNIT PER 250.32 NEC