Permit: T11EL02577

Parcel: 11107090C

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T11EL02577

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
10/21/2011 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
10/14/2011 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STILL NO SMOKE DETECTORS INSTALLED
2) DO NOT USE A BOLT TYPE DEVICE TO SPLICE GROUNDING ELECTRODE CONDUCTOR. USE A CRIMP TYPE CONNECTOR
3) PAY REINSPECTION FEE PRIOR TO NEXT INSPECTION
10/11/2011 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/30/2011 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection :*