Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2012 | ELECTRIC - FINAL | Approved | ITEMS 4,5,6 ARE NOT ELECTRICAL ISSUES BUY HOUSING ISSUES. PLUMBING WAS NOT REPLACED BUT DUG UP TO LOOK FOR A PROBLEM (TURNS OUT TUCSON WATER HAD A VALVE OFF). | |
| 03/19/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED TO ADDRESS PREVIOUS ISSUES FROM LAST INSPECTION-NOTES #4, 5 & 6 |
|
| 10/21/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SECONDARY GROUND ROD WITH APPROVED ACORN CLAMPS 2) CONTACT TEP FOR DIRECTION ON RISER. MUST BE MINIMUM 2" RISER 3) BOND WATER AND GAS LINES 4) PROVIDE PERMITS FOR PLUMBING SUPPLY LINE REPLACEMENT WITH DRAWINGS 5) ALL ADDITIONS SHOULD BE ON RECORD 6) NOTE: MIDDLE BEDROOM LACKS PROPER EGRESS TO A PUBLIC WAY 7) NOTES 1-4 FOR POWER |
|
| 09/30/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE PANEL AND RISER TO BLDG 2) MIXED BREAKER TYPE IN PANEL. INSTALL CUTTLER HAMMER BRAND TO MATCH PANEL 3) NEW PANEL VERIFY GROUND OR INSTALL GROUND ROD SYSTEM 4) WIRING TO PANEL NOT COMPLETE. LACKS MAIN DISCONNECT OVER 6 CIRCUITS 5) METAL ADDRESS TAG 6) WRONG LOCK BOX CODE LEFT NO ENTRY |