Permit: T11EL02561

Parcel: 12007766B

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/12/2011 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
10/11/2011 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
There is no access to the site.| 920*
10/04/2011 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RISER SUPPORT TO BE LISTED, - 110.26
2. OVERHEAD CONDUCTOR TO 2ND UNIT OR GUEST HOUSE TO LOW, SHOULD BE 12' ABOVE GRADE
3. GROUNDING ELECTRODE SYSTEM REQUIRED AT 2ND STRUCTURE, AS WELL AS EQUIP GROUND RMN WITH NEW FEEDER. PER 250.32
4. WIRING UNSAFE AT GUEST HOUSE.