| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2012 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/27/2012 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INTERIOR WIRING NEEDS TO BE 1 1/4" BACK FROM FINISH WALL, USE NAIL PLATES WHERE APPLICABLE 2) SUPPORT RECEPT BOX UNDER SERVICE PANEL 3) BOND GAS PIPING, PLANS AND PERMIT ? 4) SCHEDULE 80 PVC PER LAST INSPECTION 5) CKT BREAKERS MUST BE OF SAME MANUF. AS PANEL |
|
| 01/11/2012 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SCHEDULE 80 PVC OUTSIDE PER CITY OF TUCSON ORDINANCE 2) UNIT #2 NEEDS TO BE ON PERMIT 3) GROUND RODS NEED TO BE ALL IN GROUND 4) CONDUIT NEEDS TO BE SUPPORTED TO STRUCTURE, ALSO #4 BARE 5) NEED APPROVED PLANS |