Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/12/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 3/4" CONDUIT FROM PANEL (EXISTING) EP2 TO NEW LOCATION FP2B |
|
| 11/18/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | CHANGED FROM AP TO PA TO ALLOW FOR REINSPECTION | |
| 11/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS ROOMS 3, 15 & 17 2) CHECK FIRE STOPPING TO HALLS AT THAT INSPECTION |
|
| 10/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ROOMS 18, 20, 19 AND 5 WALLS-SUBJECT TO PREVIOUS INSPECTION |
|
| 10/24/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PROTECT CABLES AND FLEX AT STUDS 2) PLEASE HAVE OLD WRITE UPS ON SITE 3) HAVE ENGINEER ADDRESS 517.13 WIRING ISSUES WITH EXISTING METHODS 4) NEED TO SEE PREVIOUS ROOMS FOR FINAL TO OCCUPY 5) RECEIVED CHECK FOR $165.00 #5005 |
|
| 10/05/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | 1-ALL RECEPTACLES TO BE PER SECTION 517.13 A & B & DEVICE OUTLETS VERIFY CODE COMPLIANCY AT TIME OF INSTALLATION 2. FINISH VDV CABLING 3. OK NEW RECEPTACLES ROOMS 10, 12, 14, 16 |