Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/24/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 09/23/2011 | ELECTRIC - FINAL | Denied | REPAIR BROKEN RECEPTACLES. PROVIDE BULB PROTECTORS AT LIGHT FIXTURES. REMOVE EXTENSION CORD AT PANEL. REMOVE MC CABLE CONNECTED INTO TOP OF PANEL. ONLY ONE CONDUCTOR ALLOWED ONTO A SINGLE LUG ON A BREAKER. FILL OPEN KNOCKOUTS IN PANEL. PROVIDE ACCESS TO THE ROOF. REMOVE ABANDONED SIGN OR DISCONNECT AT SOURCE. |