Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2011 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 09/23/2011 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) METAL ADDRESS TAG METER BASE 2) PULL WEATHERED FITTINGS EXT. CONDUIT @ WATER HEATER 3) BREAKER TYPE SQUARE D MAY NOT BE USED ON SIEMENS PANEL. MIXED BREAKER TYPE 4) PROTECT AIR CONDUCTORS FROM PHYSICAL DAMAGE IN LAUNDRY UNDER 7' IN HEIGHT |