Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T11EL02489
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/01/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/26/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK NEW SUB PANEL 2) NOT ALL UNITS (HEATER) IN YET, CIRCUIT RUN TO LOCATION INTO BOX WITH COVER 3) CHANGE CKT TO 20 AMP INSTEAD OF 30 |
|
10/25/2011 | ELECTRIC - FINAL | Partial Approval | 1) BUSHING REQUIRED ON CONNECTORS FOR #4 OR LARGER 2) NEW RANGE CKTS AND RECEPTS TO BE 4-WIRE PER NEC (NEW RANGES) 3) RECALL FOR FINAL |