Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/03/2012 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CALL FOR FINAL AFTER TEP TIE IN |
|
| 01/31/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL AFTER TIE IN |
|
| 01/27/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO COMPLIANCE WITH NOTE #4 INSPECTION 1/17/12 2) A REINSPECTION FEE WILL BE ASSESED NEXT INSPECTION IF NO COMPLIANCE |
|
| 01/26/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Lock up dogs in the yard.| 910* 1) LOCK UP DOG AND RESCHEDULE INSPECTION |
|
| 01/17/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) USE LISTED RISER BRACE-SMASHED EMT CONDUIT NOT APPROVED 2) STRAP #4 BARE TO WALL 3) DO NOT SPLICE CONDUCTOR AT CHASE BY METER COMPARTMENT (ADVISED) 4) USE 1/4" MIN SIZE BOLTS TO SUPPORT RISER CONDUIT |