Permit: T11EL02447

Parcel: 136342510


Addresses:

7501 E TORONTO ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/21/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BUSHING NEEDED FOR KNOCKOUT AT BACK OF PANEL
2) NUMEROUS DIFFERENT BRANDS OF BREAKERS AT PANEL
3) ELELCTRICAL TO POOL INSTALL TO CODE OR REMOVE
4) CAP OFF UNUSED KNOCKOUTS AT BOTTOM OF PANEL
5) OUTLET IN UTILITY ROOM INSTALL TO CODE (AT CEILING)
6) WIRING IN GARAGE INSTALL TO CODE OR REMOVE
09/16/2011 ELECTRIC - FINAL Denied 1) PROVIDE A SMOKE DETECTOR IN EACH BEDROOM AND ONE OUTSIDE OF THE BEDROOMS. KEEP MINIMUM 3' AWAY FROM AIR VENTS
2) PROVIDE A BOX EXTENSION AND COVER PLATE AT RECEPT IN BEDROOM
3) SEAL OPEN KNOCKOUTS IN PANEL AND REMOVE THE NEUTRAL WIRE GOING TO NOW WHERE
4) ALL OUTDOOR RECEPTS TO GFI, INSTALLED IN OUTDOOR RATED BOXES AND CONNECTED WITH OUTDOOR TYPE FITTINGS. CLEAN OUT THE DEBRIS AND DEAD MOUSE FROM INSIDE THE PANEL