Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T11EL02439
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/28/2011 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CROSSOVER NOT COMPLETE-TEP PERMANENT TERMINATIONS NOT COMPLETE ? 2) RECALL WHEN COMPLETE, NEED TO INSPECT FINAL CONNECTION AND LOCATION FROM WINDOW TO SERVICE SPLICE |
|
10/12/2011 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) RECALL AFTER CROSS OVER |
|
10/05/2011 | ELECTRIC - SERVICE UPGRADE | Denied | FINISH ALL PREVIOUS ITEMS - A REFEE MAY BE CHARGED 1. TICHTEN SERVICE LOCKOUTS 2. TERMINATE GROUNDED CONDUCTOR 3. ARE BOTH SERVICES 1104? IF NOT, WHERE IS 1106? 4. FILL UNUSED PORTION OF PENENING IN BACK OF PANEL WITH A NON COMBUSTIBLE PRODUCT 5. MAINTAIN WORKING SPACE, SECTION 110.26 6. TIGHTEN CONDUCTOR TERMINATION 7. VERIFY SECTION 230.24 |
|
09/15/2011 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOND BUSHING REQUIRED AT SUPPLY SIDE OF SERVICE PER 250.92 NEC 2) BOND NEUTRALS IN SERVICE DISCONNECT SW'S PER 250 NEC, BOND SERVICE AS REQUIRED 3) EXPOSE GROUND RODS, WATER AND GAS BONDING 250 NEC 4) ADDRESS LABEL ON SERVICE EQUIPMENT AND LABEL DISCONNECT SWITCHES 1104 E. 7TH ST: 1) POA/SERVICE CONDUCTORS IN VIOLATION OF 230.9 NEC 2) KO SEAL AT TOP OF SERVICE ENCLOSURE NOT RAIN TITE 110.26 NEC 3) ? BOX COVER WITH SELF TAPPING SCREW NOT APPROVED AS COVER OR REPAIR TO DEADFRONT COVER VOIDS LISTING OF MANUF. 110.26 NEC 4) BUSHING REQUIRED ON 2" CONDUIT CONNECTION ON SIDE OF SERVICE PANEL 300 NEC 5) #6 GROUND WIRE REQUIRED TO BE GREEN IN COLOR FULL LENGTH AS REQUIRED BY 250 NEC 6) METER ENCLOSURE NEEDS TO BE OPENED FOR INSPECTION. TEP TO REMOVE SEAL 7) BUSHING REQUIRED IN SUB PANEL 2" CONNECTION 300 NEC 8) #8 AWG CONDUCTORS ON 60 AMP BREAKER 310.15 NEC 9) EXPOSE GROUND RODS/WATER, GAS AND BONDS |