Permit: T11EL02439

Parcel: 124060850


Addresses:

1104 E 7TH ST


Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T11EL02439

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Partial Approval

Date Description Inspector Results Comments
10/28/2011 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) CROSSOVER NOT COMPLETE-TEP PERMANENT TERMINATIONS NOT COMPLETE ?
2) RECALL WHEN COMPLETE, NEED TO INSPECT FINAL CONNECTION AND LOCATION FROM WINDOW TO SERVICE SPLICE
10/12/2011 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) RECALL AFTER CROSS OVER
10/05/2011 ELECTRIC - SERVICE UPGRADE Denied FINISH ALL PREVIOUS ITEMS - A REFEE MAY BE CHARGED
1. TICHTEN SERVICE LOCKOUTS
2. TERMINATE GROUNDED CONDUCTOR
3. ARE BOTH SERVICES 1104? IF NOT, WHERE IS 1106?
4. FILL UNUSED PORTION OF PENENING IN BACK OF PANEL WITH A NON COMBUSTIBLE PRODUCT
5. MAINTAIN WORKING SPACE, SECTION 110.26
6. TIGHTEN CONDUCTOR TERMINATION
7. VERIFY SECTION 230.24
09/15/2011 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) BOND BUSHING REQUIRED AT SUPPLY SIDE OF SERVICE PER 250.92 NEC
2) BOND NEUTRALS IN SERVICE DISCONNECT SW'S PER 250 NEC, BOND SERVICE AS REQUIRED
3) EXPOSE GROUND RODS, WATER AND GAS BONDING 250 NEC
4) ADDRESS LABEL ON SERVICE EQUIPMENT AND LABEL DISCONNECT SWITCHES
1104 E. 7TH ST:
1) POA/SERVICE CONDUCTORS IN VIOLATION OF 230.9 NEC
2) KO SEAL AT TOP OF SERVICE ENCLOSURE NOT RAIN TITE 110.26 NEC
3) ? BOX COVER WITH SELF TAPPING SCREW NOT APPROVED AS COVER OR REPAIR TO DEADFRONT COVER VOIDS LISTING OF MANUF. 110.26 NEC
4) BUSHING REQUIRED ON 2" CONDUIT CONNECTION ON SIDE OF SERVICE PANEL 300 NEC
5) #6 GROUND WIRE REQUIRED TO BE GREEN IN COLOR FULL LENGTH AS REQUIRED BY 250 NEC
6) METER ENCLOSURE NEEDS TO BE OPENED FOR INSPECTION. TEP TO REMOVE SEAL
7) BUSHING REQUIRED IN SUB PANEL 2" CONNECTION 300 NEC
8) #8 AWG CONDUCTORS ON 60 AMP BREAKER 310.15 NEC
9) EXPOSE GROUND RODS/WATER, GAS AND BONDS