Permit: T11EL02376

Parcel: 140411260

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Permit Number - T11EL02376

Inspection Description - ELECTRIC - TEMPORARY SERVICE

Inspection Status - Approved

Date Description Inspector Results Comments
01/04/2012 ELECTRIC - TEMPORARY SERVICE Approved
12/05/2011 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection :*
1) LOADS NOT CONNECTED YET-CALL FOR INSPECTION WHEN READY
11/29/2011 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE LETTER OF TORQUE FOR EQUIP. TORQUED PER MANUFACTURE SPEC BY CONTRACTOR
2) BRACE SERVICE ENTRANCE CONDUCTORS PER NOTE ON PLAN E-20
3) CONTACTOR TO OPEN ALL EQUIPMENT AS NECESSARY FOR INSPECTION OF SES EQUIP, J-BOX, FEEDERS AND PANELS INSTALLED
4) NEED BUSHINGS AT CONDUIT ENDS, PER 600.4 & 352.46 NEC
5) HOUSE KEEPING PAD TO SMALL, SES EQUIP EXTENDS APPROX 1 1/4" BEYOND PAD 110.12 NEC
6) ANCHOR CABINET PER MANUFACTURE