Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2011 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 09/08/2011 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OUTLET COVER PLATES NEEDED THRU OUT 2) BLANK OFF UNUSED KNOCKOUTS AT DEAD FRONT AND PANEL BOX 3) PANEL DOOR NOT SHUTTING 4) EXPOSED WIRES AT WALL OF GREAT ROOM (GREEN). NEEDS TO BE CONCEALED IN JUNCTION BOX WITH COVER THAT IS ACCESSIBLE. |