Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/20/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/16/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) 50 AMP BREAKER MUST BE GUTLER-HAMMER |
|
| 09/15/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SEE NOTE #1-BREAKER MUST BE OF SAME MANUF. AS PANEL |
|
| 09/08/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VERIFY THAT MIXED BREAKERS AT SERVICE AND PANEL ARE COMPATIBLE 2) INSTALL CORRECT FLEX CONNECTION AFTER WATER HEATER 3) TERMINATE CEILING WIRES IN BOX WITH COVER OR INSTALL FIXTURE |