Permit: T11EL02349

Parcel: 118033540

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/08/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/06/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) MINIMUM DISTANCE BETWEEN GROUND RODS IS 6'
2) EXTERIOR LIGHT FIXTURE BROKEN AND REMOVE OR REPLACE
3) OUTLET ABOVE KITCHEN AND BATH COUNTERS ARE TO BE GFI PROTECTED
4) PROVIDE SMOKE ALARMS IN ALL BEDROOMS
5) BATHROOM FIXTURE MISSING SAFETY GLOBE