Permit: T11EL02222

Parcel: 11201029A


Addresses:

2601 E ALLEN RD

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
09/08/2011 ELECTRIC - UFER Approved IVRS - Inspection :*
08/25/2011 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CAN NOT IDENTIFY CONDUCTOR SIZE APPEARS TO BE #8 TOO SMALL FOR GO AMP AMPACITY
2. TIGHTEN STRANDED CONDUCTOR TERMINATIONS
3. USE APPOVED RISER PARTS NOT STRAP
4. LABEL BREAKER
5. NEUTRAL CONDUCTER TOO SMALL
6. VERIFY SUV LIGHT RESISENT MARKINGS ON CONDUCTORS
7. STRAP GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE
8. WATER BOND TO BE TO INTERIOR PIPING
9. SERVICE ENERGIZED WITHOUT CLEARANCE
10. WHERE IS GAS BOND