Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2011 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
| 08/25/2011 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CAN NOT IDENTIFY CONDUCTOR SIZE APPEARS TO BE #8 TOO SMALL FOR GO AMP AMPACITY 2. TIGHTEN STRANDED CONDUCTOR TERMINATIONS 3. USE APPOVED RISER PARTS NOT STRAP 4. LABEL BREAKER 5. NEUTRAL CONDUCTER TOO SMALL 6. VERIFY SUV LIGHT RESISENT MARKINGS ON CONDUCTORS 7. STRAP GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE 8. WATER BOND TO BE TO INTERIOR PIPING 9. SERVICE ENERGIZED WITHOUT CLEARANCE 10. WHERE IS GAS BOND |