Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/23/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/16/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GAS PIPING IS TO BE BONDED ONLY-CANNOT USE AS A GROUNDING 2) SYSTEM NEEDS 2 GROUND RODS 6' APART 3) COMPLETE ALL ITEMS AS CALLED OUT PRIOR TO NEXT RECALL OR A REFEE WILL APPLY, IF NOT READY |
|
| 08/17/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING SMOKE DETECTORS IN SLEEPING ROOMS/HALL 2) MISSING FACE PLATES AT RECEPTS 3) WIRES AT STORAGE NOT TO CODE 4) MISSING DEAD FACE AT MAIN 5) NEUTRAL AT MAIN BEING USED AS A UNGROUNDED CONDUCTOR 6) NEED TO RE-ATTACH LNMF AT MAIN AND STRAP TO WALL 7) PLUG ALL HOLES NOT BEING USED AT MAIN 8) NO GROUNDING SYSTEM AT MAIN 9) ALL ELECTRIC NEEDS TO BE SAFE TO RELEASE |