Permit: T11EL02192

Parcel: 136171270

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/23/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/16/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GAS PIPING IS TO BE BONDED ONLY-CANNOT USE AS A GROUNDING
2) SYSTEM NEEDS 2 GROUND RODS 6' APART
3) COMPLETE ALL ITEMS AS CALLED OUT PRIOR TO NEXT RECALL OR A REFEE WILL APPLY, IF NOT READY
08/17/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING SMOKE DETECTORS IN SLEEPING ROOMS/HALL
2) MISSING FACE PLATES AT RECEPTS
3) WIRES AT STORAGE NOT TO CODE
4) MISSING DEAD FACE AT MAIN
5) NEUTRAL AT MAIN BEING USED AS A UNGROUNDED CONDUCTOR
6) NEED TO RE-ATTACH LNMF AT MAIN AND STRAP TO WALL
7) PLUG ALL HOLES NOT BEING USED AT MAIN
8) NO GROUNDING SYSTEM AT MAIN
9) ALL ELECTRIC NEEDS TO BE SAFE TO RELEASE