Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/07/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/03/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RELOCATE SMOKE DETECTOR TO PROPER LOCATION OUTSIDE BEDROOMS 2) CALL FOR FINAL TO CHECK GROUNDING OF OUTLETS |
|
| 08/09/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WHITE 40 AMP HOT LEAD MUST BE RED OR BLACK. BLANK COVER UNUSED OPENINGS DEAD FRONT. LABEL CIRCUITS 2) MISSING A/C CONDENSOR DUE TO VANDALISM. EXPOSED WIRING HAZARDOUS. REQUIRES PERMIT FOR REPLACEMENT 3) SMOKE ALARM BEDROOMS AND HALLWAY 4) EXPOSED CONDUCTORS ALL BEDROOMS AT MINI SPLITS VANDALISM 5) 3 WIRE OUTLETS WITH GROUND ON UNGROUNDED CIRCUITS THROUGHOUT 6) REPLACE DAMAGED BURNED OUTLET EAST BATHROOM 7) HAZARDOUS EXPOSED ROMEX IN ? ROOM NOT TO CODE. OFF KITCHEN AND SUB PANEL 8) CONSULT WITH QUALIFIED ELECTRICIAN TO BRING HOME UP TO CODE 9) UNDERGROUND AT PORCH JUNCTION NOT TO CODE 7) |