Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/27/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NOTE 8 FROM PREVIOUS
2) NO ENTRY
3) RECALL 02090
10/27/2011 ELECTRIC - FINAL Approved
08/08/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) METAL ADDRESS TAG METER
2) LABEL ALL CIRCUITS
3) EXPOSE SECONDARY GROUND ROD
4) PROVIDE CONTINOUS #4 CONDUCTOR TO GUTTER IF SHARED GROUND SYSTEM TO BE USED WITH COMPRESSION FITTING OR WELD. NO SPLIT BOLT
5) MISSING WEATHERED COVER 220 EXTERIOR
6) VANDALIZED ROMEX EXTERIOR-OVERHANG AT STORAGE
7) ROMEX ADDED TO FRONT LIGHT FIXTURE NOT TO CODE
8) SMOKE ALARM HALLWAY
9) WATER HEATER NOT INSTALLED TO CODE
126 E. AJO WAY:
1) METAL ADDRESS TAG METER
2) LABEL ALL CIRCUITS
3) EXPOSE SECONDARY GROUND ROD
4) WIRING ADDED TO EXTERIOR LIGHTING AT OVERHANG AND CARPORT NOT TO CODE AND INSTALLED WITHOUT PERMIT
5) WIRING IN STORAGE NOT TO CODE. PROTECT FROM PHYSICAL DAMAGE AND SECURE TO CODE ALL ROMEX UNDER 7'
6) WATER HEATER NOT INSTALLED TO CODE
7) B-VENT IMPROPER MATERIAL AND TPR LINE MUST BE CVPC OR COPPER 3/4" TO EXTERIOR