Permit: T11EL02081

Parcel: 113072350

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/18/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/13/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) CANNOT TRIM OR FORK CONDUCTORS
09/07/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PANEL LABELING TO BE PER 408.4-ALL BREAKERS
2) ANTI OXIDE COMPUND NEEDED ON ALL ALUMINUM CONDUCTORS
3) SEPEATE AND INSTALL EQUIPMENT GROUNDING CONDUCTORS PER PANEL INSTRUCTIONS
4) TIGHTEN LOOSE FITTINGS
5) SECURELY ATTACH NM CABLES TO BACK OF BOX 312.5 (C)
08/23/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*