Permit: T11EL02054

Parcel: 125090150


Addresses:

2617 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
08/09/2011 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
08/04/2011 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/03/2011 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
1) GROUNDING ELECTRODE MISSING AND BONDING TO WATER AT SERVICE
2) BLDG SERVICE TO HAVE 3' WORKING SPACE 110.32
3) STILL HAVE TO INSPECT IN SIDE OF BLDG
08/02/2011 ELECTRIC - RECONNECT Denied NO ACCESS INTO SITE. INSPECTIONS ARE DONE BETWEEN 7:30 AM AND 3:00 PM. PLEASE HAVE SOMEONE ON SITE DURING THOSE HOURS FOR US TO COMPLETE THIS INSPECTION.