Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2011 | ELECTRIC - FINAL | Approved | ||
| 07/27/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RAISE ALL SMOKE DETECTORS TO MANUFACTURES SPECS FROM CEILING 2) SMOKE DETECTOR IN HALL NOT WORKING 3) UNDERSIZED CONDUCTORS FOR 50 AMP BREAKER AT PANEL 4) HOT (BLACK) WIRE GOING TO GROUND BAR AT PANEL 5) 2 CONDUCTORS TO ONE BREAKER NOT ALLOWED AT PANEL |