Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/04/2011 | ELECTRIC - FINAL | Approved | SCOPE FOR THIS PERMIT COMPLETE. DO NOT CLEAR SERVICE WITH THIS ACTIVITY | |
| 08/02/2011 | ELECTRIC - FINAL | Partial Approval | REPL OF MAIN BREAKERS OK NOT OK TO CLEAR ELEC. NEED PERMIT TO RECONNECT, REPAIR/REPLACE AND REWIRE ELEC IN BLDG. BLDG IS IN HAZARDOUS CONDITION. |
|
| 07/29/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPOSED GROUND RODS 2) GROUNDING ELECTRODE CONDUCTOR NEEDS TO BE CONTINOUS, NO SPLICES 3) PROTECT CONDUCTORS (BUSHINGS) 4) IS GAS BONDED ? 5) IS THIS (2) UNIT LABEL PANEL ADDRESSED PROPERLY WITH CITY |