Permit: T11EL01864

Parcel: 13704117B


Addresses:

5653 S NOGALES HY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/24/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/08/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) POST UNIT NUMBERS VISIBLE FROM STREET
2) LABEL CIRCUITS
3) SEAL UNUSED OPENINGS DEAD FRONT
4) MISSING EXT. LIGHT FIXTURE
5) EXPOSED ROMEX EXT. GFCI BOX
6) SECURE ALL ROMEX AT SUB PANEL
7) EXPOSED ROMEX AT SUB PANEL PROTECT FROM PHYSICAL DAMAGE
07/29/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
1) CALLED AND LEFT MESSAGE PER REQUEST-NO RETURN CALL
2) GATE LOCKED
3) PAY REFEE AT 201 N. STONE PRIOR TO NEXT INSPECTION
07/27/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1) GATE LOCKED-NO MSG
2) A REINSPECTION FEE WILL BE ASSESED NEXT INSPECTION IF NO ACCESS OR CODE COMPLIANCE
3) RESCHEDULE INSPECTION
07/19/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) WIRING AT PANEL LOADS NOT TO CODE
2) OBTAIN THE SERVICES OF A LICENSED OR QUALIFIED ELECTRICIAN TO DO WORK