Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/20/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection 1) RISER HUB NOT GROUNDED 250 NEC 2) NEED HOLDOWN PER 408 NEC MAIN BRKR 3) A REINSPECTION FEE IS ASSESED-4TH INSPECTION, NO COMPLIANCE. PAY REFEE AT 201 N. STONE |
|
| 07/19/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO COMPLIANCE WITH NOTES #2,4 & 5-PROVIDE LADDER NEXT INSPECTION RE-INSPECTION FEE NEXT INSPECTION IF NO COMPLIANCE |
|
| 07/13/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/11/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) RISER BRACE NOT LISTED 2) HUB ON RISER NOT RATED FOR BONDING AT SERVICE 3) NO BUSHING ON OFF SET NIPPLES 4) NEED HOLDOWN DEVICE FOR BACK FED MAIN BREAKERS 5) NO EQUIP. GROUNDS IN FLEX FOR LOADS 6) RISER CONDUIT NOT SUPPORTED TO STRUCTURE 7) NO LOAD BREAKERS INSTALLED YET. ALL SERVICE IS NEW |