Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/07/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SMOKE DETECTORS NEEDED IN ALL BEDROOMS AND ADJACENT HALL 2) PHYSICAL PROTECTION NEEDED ON CONDUCTORS BELOW 7' 3) BLANK SPACERS NEEDED ON OPEN KNOCKOUTS AT PANEL 4) NUMEROUS VIOLATIONS IN PANEL NEED TO BE BROUGHT UP TO CODE 5) SUPPORT RISER 6) COVER OPEN OUTLETS WITH COVER PLATES |