Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/07/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) REPLACE MISSING GEC AT SERVICES A, B AND C |