Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T11EL01702
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/29/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/26/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STRAP RISER 2) PANEL LABELING TO BE PER 408.4-NO GENERAL LABELING 3) CONDUCTOR SPLICE TO BE SAME SIZE AS ORIGINAL CONDUCTOR |
|
06/23/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND RODS TO BE MINIUM 8' - EVIDINCE OF CUT 2) CABLE SHEATHING TO EXTEND 1/4" INTO PANEL 3) FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NEW COMBUSTABLE PRODUCT TO PREVENT SPREAD OF FIRE. 4) DAMAGED AND BURNT CONDUCTORS 50 SECURE BOND CONDUCTORS TO STRUCTURE 6) LABEL CIRCUITS |