Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2011 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 06/09/2011 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BLANK OFF UNUSED KNOCK OUT AT BOTTOM OF SUB PANEL AND MAIN PANEL 2) SECURE SUB PANEL TO WALL 3) FLAT TIPPED SCREWS NEEDED TO FASTEN DEADFRONT TO SUB PANEL 4) GROUNDS AND NEUTRALS TO BE SEPERATED ON SUB PANEL 5) CONDUCTOR JACKET TO GO INTO CONNECTOR FOR FEEDER TO SUB PANEL 6) LABEL PANELS FOR CIRCUITS 7) BUSHING NEEDED FOR BACK OF PANEL FOR CONDUCTOR HOME RUNS 8) CONSULT WITH TEP FOR CONDUCTORS OVER PATIO ROOF 9) WIRING TO DETACHED ACCESSORY BLDG WITH ELECTRIC NOT TO CODE |