Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/28/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/15/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) RECALL AFTER CROSS OVER 2) LABEL CIRCUITS 3) PROPER BREAKERS |
|
| 06/14/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) SECURE #4 TO BLDG 2) RECALL 02090 |
|
| 06/10/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND RODS MINIMUM 6' APART 2) METAL ADDRESS TAG METER BASE 3) PROVIDE WATER AND GAS BONDS 4) MAIN FEEDERS PER TEP 24" LENGTH AT WEATHER HEAD FEEDERS TO SHORT 5) SECURE PANEL PER CODE 6) SEAL UNUSED OPENINGS 7) BENDS IN MAIN FEEDERS NOT TO CODE 8) CONTACT QUALIFIED ELECTRICIAN 9) STOPPED INSPECTION |