Permit: T11EL01549

Parcel: 113010400


Addresses:

1340 E ROGER RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/22/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK ELECTRIC
06/09/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PLEASE VERIFY 2ND GROUND ROD
2) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS
3) RISER HARDWARE TO BE 1/4" MINIMUM
4) SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL
5) THIS IS A SERVICE UPGRADE