Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T11EL01539
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/16/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
06/14/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED BOND BUSHING SERVICE NIPPLE 250.92 2) PROTECT CONDUCTOR 352.46 & 300.4 3) SUPPORT 1/2" CONDUIT UNDER PANEL 4) LABEL PER 408.4 |