Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/20/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MANY ADDED CIRCUITS TO 60 AMP INSTALLED WITHOUT PERMIT. HAZARDOUS WIRING DBL LUGGED WIRING OVERLOADS MAIN. ADDED 40 AMP DRY AND RANGE CIRCUIT & 7 15 OR 20 AMP CIRCUITS WITHOUT MAIN DISCONNECT. INCREASE REQUIRED OR RETURN TO ORIGINAL STATE 2) OMIT EXTERIOR LIGHTING ON ZIP CORDS 3) EXTERIOR GFCI ON APPROVED LISTED BOXES 4) NO INTERIOR INSPECTION AT THIS TIME |