Permit: T11EL01403

Parcel: 124051780


Addresses:

1118 E 6TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/08/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK ELECTRIC
05/31/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
05/26/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING FUSES-NEED SERVICE RATED FUSES AND REJECTION PINS
2) OUTSIDE PANEL "C": FILL UNUSED OPENINGS, PROPERLY INSTALL AND SUPPORT SWITCH IN SEAL TITE AND USE BREAKERS LISTED BY MANUFACTURE
3) CANNOT USE SHEETMETAL SCREWS FOR GROUNDING 250.8
4) INSIDE PANEL: HIGH LEG ? IF SO BREAKER ARRAINMENT, HANDLE TIE, WARNING LABEL AND PANEL DIRECTORY
5) FINISH PREVIOUS ITEMS
05/19/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LABEL SERVICE EQUIPMENT AT METER
2) FILL UNUSED OPENINGS IN BOXES AND PANELS
3) EXTENSION CORD NOT ALLOWED FOR PERMANENT WIRING METHODS
4) PROPERLY INSTALL AND SUPPORT RACEWAYS
5) RECEPTS IN INDUSTRIAL COVER TO BE PER 406 (NEW WORK)
6) BOXES OPEN AND LOOSE FITTINGS
7) PLEASE VERIFY FAN RATED BOXES