Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
| 05/31/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 05/26/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING FUSES-NEED SERVICE RATED FUSES AND REJECTION PINS 2) OUTSIDE PANEL "C": FILL UNUSED OPENINGS, PROPERLY INSTALL AND SUPPORT SWITCH IN SEAL TITE AND USE BREAKERS LISTED BY MANUFACTURE 3) CANNOT USE SHEETMETAL SCREWS FOR GROUNDING 250.8 4) INSIDE PANEL: HIGH LEG ? IF SO BREAKER ARRAINMENT, HANDLE TIE, WARNING LABEL AND PANEL DIRECTORY 5) FINISH PREVIOUS ITEMS |
|
| 05/19/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LABEL SERVICE EQUIPMENT AT METER 2) FILL UNUSED OPENINGS IN BOXES AND PANELS 3) EXTENSION CORD NOT ALLOWED FOR PERMANENT WIRING METHODS 4) PROPERLY INSTALL AND SUPPORT RACEWAYS 5) RECEPTS IN INDUSTRIAL COVER TO BE PER 406 (NEW WORK) 6) BOXES OPEN AND LOOSE FITTINGS 7) PLEASE VERIFY FAN RATED BOXES |