Permit: T11EL01368

Parcel: 130102510


Addresses:

3111 E 29TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/31/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/17/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FRONT ENTRY LIGHTS OUTSIDE NOT WIRED TO CODE-EXPOSED WIRING, IMPROPER CONNECTION TO LIGHT FIXTURE. ALSO CARPORT LTG., SECURITY LTG., ZIP CORD NOT APPROVED AS PERMANENT WIRING METHOD (CARPORT)
2) RANGE HOODE NOT WIRED TO CODE
3) INSTALL SMOKE DETECTORS IN BEDROOMS
4) CEILING FANS NOT WIRED TO CODE
5) WIRING IN BACK PORCH NOT TO CODE, EXPOSED ROMEX BELOW CEILING, WORK DONE WITHOUT PERMIT, ALSO OPEN PORCH IN BACK OF HOUSE
6) GROUNDS AND NEUTRALS TO BE ISOLATED IN SUB PANEL
7) EXPOSED ROMEX, OPEN ENDS AT SERVICE EQUIPMENT
8) ADVISE OWNER TO INSTALL GFI PROTECTED RECEPTS IN BATHROOMS AND KITCHEN COUNTERS
05/16/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) MANY ADDED EXTERIOR LIGHT FIXTURES NOT TO CODE
2) EAST CARPORT ON PROPERTY LINE
3) PROVIDE ACCESS TO UNIT