Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T11EL01367
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/09/2011 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
05/16/2011 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ADDED 12-2 WIRING TO ROOF TOP UNDER SIZED FOR 30 AMP BREAKER TO A/C UNIT. WHITE HOT LEAD, NEEDS TO BE RED OR BLACK 2) CAP MISSING LIGHT FIXTURES OR INSTALL FIXTURES 3) OMIT HAZARDOUS ZIP CORD MASTER BEDROOM CEILING FAN |