Permit: T11EL01347

Parcel: 131114210


Addresses:

5663 E 36TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/16/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/12/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BLANK OFF OPEN BREAKER KNOCK OUT AT PANEL
2) UNDERSIZED CONDUCTOR (14) FOR 20 AMP BREAKER AT PANEL
3) BUSHING NEED AT BACK OF PANEL AT CONDUCTOR ENTRANCE
4) KITCHEN BOXES, OUTLETS AND COVER PLATES INSTALLED TO CODE
5) SMOKE DETECTORS NEEDED IN ALL BEDROOMS AND ADJACENT HALL