Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2011 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* 1) UFERS OK, OK TO TIE IN POWER |
|
| 05/10/2011 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) METAL ADDRESS TAG 2) BOND GAS AND WATER 3) BRACE RISER OVER 30" IN HEIGHT 4) SECURE #4 TO BLDG |
|
| 05/09/2011 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) CANCELED PER MEMO |