Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2011 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 10/12/2011 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) BREAKER AMPACITY FOR #8 NM CABLE ONLY 40 AMP 2) SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL |
|
| 09/08/2011 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL AFTER TIE IN |
|
| 09/07/2011 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) NEED BONDING BUSHING ON RISER |